BENV0140 Chap.2 Heat Transfer and Fabric Performance
Heat Transfer and Fabric Performance
Heat Transfer and Fabric Performance converts building geometry and thermal properties into a heat-loss rate. The second law gives the direction from warmer to colder regions. Each exposed element contributes its U-value multiplied by area, measured in watts per kelvin. Adding walls, roofs, floors, windows and doors across the chosen boundary gives the fabric heat-transfer coefficient.
Multiplying that coefficient by the indoor-outdoor temperature difference produces power; multiplying power by duration produces energy. The method depends on correct opening areas, consistent units and explicit assumptions about adjacent spaces and steady conditions. Reliable calculations begin with a sketch that marks every heat-flow surface and subtracts openings from opaque elements once, not twice.
The coefficient in watts per kelvin is a property of the selected envelope, whereas the heat-loss rate changes with the chosen temperature difference. This distinction makes scenario testing transparent: insulation changes a U-value, glazing replacement changes both area allocation and performance, and weather changes the driving condition.
Thermal bridges and non-steady effects may require additional treatment, so a simplified result should state what it omits. Sanity checks compare component shares, units and order of magnitude before the result is used to size plant or assess retrofit priorities.
What this chapter covers
- 01
Thermodynamic direction
- 02
R-values and U-values
- 03
Element areas
- 04
Fabric HTC
- 05
Temperature difference
- 06
Power and energy
Worked example · free
Calculate fabric loss for a studio
- 3Calculate element coefficients of 14.85, 5.40 and 6.00 W/K.
- 1Add them to obtain a fabric HTC of 26.25 W/K.
- 2Use the 16 K temperature difference to obtain 420 W of heat-loss power.
- 1State that ventilation and plant efficiency are outside this fabric boundary.
Key terms
- Thermal transmittance
- Heat-transfer rate per unit area and per kelvin across an element.
- Fabric HTC
- The summed fabric heat-transfer coefficient across a chosen envelope boundary.
- Adiabatic boundary
- An idealised boundary across which no net heat transfer occurs.
Heat Transfer and Fabric Performance FAQ
Why is window area subtracted from wall area?
The window replaces part of the wall and has its own U-value. Using the gross wall area and then adding the window counts that patch twice. Calculate the opaque area first, then add each opening as a separate U times area term.
What is the difference between HTC and heat-loss power?
HTC is measured in watts per kelvin and describes the envelope sensitivity to temperature difference. Multiplying by the stated indoor-outdoor difference produces watts of heat-transfer power for those conditions. Energy requires an additional time interval.
Which assumptions should I mention?
State the boundary, temperatures, whether conditions are treated as steady, how adjacent spaces are handled and where U-values come from. If ventilation, thermal bridges, gains or plant efficiency are excluded, name that exclusion before interpreting the result.
Exam move
Draw the building boundary and list every surface that separates unlike temperatures. Convert dimensions into areas and mark openings before using any U-value. Build a table with element, net area, U-value and U times area contribution; the table makes double counting visible. Sum the contributions in W/K, then introduce temperature difference to obtain watts.
Only after that step should you multiply by duration and convert to kilowatt-hours. Practise reverse checks by dividing power by temperature difference and comparing the recovered coefficient with the element sum. Use contribution shares to identify which path dominates, but avoid turning the largest term into an automatic retrofit recommendation.
Feasibility, moisture, disruption, embodied impact and cost require a wider decision boundary. Keep an error log for gross area, internal surface, missing opening, unit conversion and temperature sign. For explanation questions, link conduction, convection and radiation to the building element and use a labelled diagram. Finish with the physical meaning and one observation that could test the modelled result.
Rework one geometry three ways: first with no openings, then with a high-U window, then with an improved window. Compare both the absolute coefficient and the share from each element. This shows why a small surface can matter and why contribution depends on area as well as transmittance. Change indoor and outdoor temperatures while keeping the envelope fixed so the distinction between HTC and power becomes automatic.
Follow with an operating-duration change to separate power from energy. Build one deliberately wrong solution that adds window area without subtracting it, and quantify the overstatement. For conceptual revision, sketch the thermal path across a wall and label surface conditions, layers and the direction of transfer.
Explain when an adjacent space might be treated as adiabatic and why that is an assumption rather than a property of the wall. Compare specified, modelled and measured U-values, noting how construction defects, thermal bridges and uncertainty can create disagreement. End a session by drafting a retrofit paragraph that uses the calculation as evidence but also checks moisture, disruption and whole-life consequences.
That combination prepares you to move from a controlled physics calculation to a defensible building decision.