EE509 Chap.8 Paschen Law and Corona Performance
Paschen Law and Corona Performance
Paschen behaviour has one physical minimum
Spark voltage depends on pressure-distance product and gas density. Below the minimum, collisions are too rare for efficient ionization. Above it, collisions are frequent but electrons gain less energy between them.
Both branches therefore require higher voltage than the balance point.
Corona is a local non-uniform-field discharge
Ionization begins near conductor surfaces and sharp points before a complete gap spark. Disruptive critical voltage marks onset, while visible inception is higher. Larger effective radius, smoother surface and bundled conductors reduce surface stress.
Corona adds lossy current and electromagnetic interference. A line calculation must use phase voltage, density correction, geometry, threshold comparison and the validity range of the selected empirical loss formula.
What this chapter covers
- 01
Pressure-distance product
- 02
Paschen minimum and two branches
- 03
Temperature and gas-density correction
- 04
Disruptive critical voltage
- 05
Visible corona inception
- 06
Peek and Peterson loss ranges
- 07
Line-calculation protocol: convert system voltage to the required phase quantity, distinguish radius from diameter, correct gas density with absolute temperature, preserve threshold order, compare operation with onset, select an empirical relation from its validity ratio, and scale per-phase per-length loss only after its unit is confirmed
Worked example · free
Make the phase-voltage decision first
- 2Convert line to phase voltage.
- 2Compare phase voltage with the threshold.
- 2State whether a corona-loss formula should be applied as established corona.
Key terms
- Paschen Curve
- The relationship between gas spark voltage and pressure-distance product in a uniform field.
- Disruptive Critical Voltage
- The threshold at which local gas ionization and corona begin around a conductor.
- Visual Inception Voltage
- The higher threshold at which corona produces visible luminescence.
- Density Correction
- Adjustment for the effect of pressure and absolute temperature on gas density and corona threshold.
Paschen Law and Corona Performance FAQ
Why does voltage rise on both sides of the Paschen minimum?
At low pressure-distance product, electrons make too few collisions. At high product, collisions are frequent but energy gained between them is smaller. The minimum balances collision opportunity with energy per free path.
Why is visual corona voltage higher than disruptive voltage?
Disruptive voltage marks the start of ionization. Visible light requires enough excitation and discharge development to produce luminescence, so it appears only after the lower onset threshold has been exceeded.
Which checks come before a corona-loss formula?
Convert line to phase voltage, use radius rather than diameter, correct gas density with absolute temperature, calculate the disruptive threshold and test the empirical formula's stated voltage-ratio range. Skipping those checks can invalidate otherwise accurate arithmetic.
Exam move
Sketch the Paschen curve and explain each branch without formulas. Then work a line setup in a fixed order: phase conversion, radius, density correction, disruptive voltage, visual inception, operating comparison and loss-formula validity. Keep units on every intermediate line and state whether corona is expected before calculating any loss. Annotate the Paschen sketch with collision reasoning.
On the low pressure-distance side, electrons encounter too few molecules across the gap, so a larger voltage is needed to produce enough ionization. On the high side, collisions are frequent but the energy gained between them is smaller, so voltage must again rise. Mark the minimum as the balance between collision opportunity and energy acquisition.
Use this explanation to reject the false idea that reducing pressure always improves insulation. For corona work, create a data ledger before selecting a formula. Record whether the system voltage is line-to-line or phase-to-neutral, whether conductor size is radius or diameter, whether spacing is centre-to-centre, and which pressure and absolute temperature units the density correction requires.
Convert line voltage to phase voltage once and label its rms or peak convention. Calculate disruptive critical voltage and visible inception separately; the disruptive threshold should be lower for the same stated condition. Decide whether the operating point is below onset, between thresholds or above visible inception. Only after that decision compute a loss-formula validity ratio and choose the empirical branch.
Do not select Peek or Peterson because one output appears reasonable. Scale a valid result in visible stages: per phase per unit length, one phase over the stated distance, then the total number of phases. Retain one power unit until the end.
Complete an error triage for any implausible result by checking phase conversion, radius versus diameter, density correction, threshold order, empirical range, length and phase multipliers. Finish with a physical interpretation. Corona can create audible noise and electromagnetic interference even when calculated power loss is modest, while smoother or bundled conductors reduce surface stress by increasing effective radius.
This links the arithmetic to the reason a line designer controls geometry and surface condition.
Working through Paschen Law and Corona Performance in EE509? Sia is AskSia’s AI Electrical Engineering tutor — ask any EE509 Paschen Law and Corona Performance question and get a clear, step-by-step explanation grounded in how EE509 is taught and assessed. Read this chapter free, then take your hardest questions to Sia.